Request a Quote

Prime-Rated Containerized Power Stations

750 – 2,500 kVA · Containerized Power Stations

Prime-Rated Containerized Power Stations — 750 – 2,500 kVA
Containerized Power Stations · 750 – 2,500 kVA

Prime-rated containerized power stations from 750 to 2,500 kVA.

Prime-rated containerized power stations built into ISO containers for plants, mines and remote sites: 13 models from 750 to 2,500 kVA at 50 Hz, with 60 Hz versions on request.

Models

Models of Prime-Rated Containerized Power Stations at 50 Hz
Model Prime Standby Engine Rated current (A) Fuel at full load (L/h) L × W × H (mm) Weight (kg) Inquire
WBC-750P 600 kW / 750 kVA 660 kW / 825 kVA 12M33D748E310 1083 148.2 6058 × 2438 × 3151 10500 Inquire
WBC-800P 640 kW / 800 kVA 704 kW / 880 kVA 12M33D792E310 1155 158.1 6058 × 2438 × 3151 10500 Inquire
WBC-900P 720 kW / 900 kVA 792 kW / 990 kVA 12M33D902E310 1299 177.9 6058 × 2438 × 3151 10940 Inquire
WBC-1000P 800 kW / 1,000 kVA 880 kW / 1,100 kVA 12M33D968E310 1443 197.6 6058 × 2438 × 3151 10940 Inquire
WBC-1125P 900 kW / 1,125 kVA 990 kW / 1,237.5 kVA 12M33D1108E310 1624 220.2 6058 × 2438 × 3151 11400 Inquire
WBC-1250P 1,000 kW / 1,250 kVA 1,100 kW / 1,375 kVA 12M33D1240E310 1804 244.7 6058 × 2438 × 3151 11700 Inquire
WBC-1500P 1,200 kW / 1,500 kVA 1,320 kW / 1,650 kVA 16M33D1530E310 2165 290.8 12192 × 2438 × 3500 16480 Inquire
WBC-1650P 1,320 kW / 1,650 kVA 1,452 kW / 1,815 kVA 16M33D1580E310 2382 319.9 12192 × 2438 × 3500 16580 Inquire
WBC-1750P 1,400 kW / 1,750 kVA 1,540 kW / 1,925 kVA 16M33D1680E310 2526 339.3 12192 × 2438 × 3500 16850 Inquire
WBC-1875P 1,500 kW / 1,875 kVA 1,650 kW / 2,062 kVA 16M33D1800E310 2706 363.5 12192 × 2438 × 3500 17050 Inquire
WBC-2000P 1,600 kW / 2,000 kVA 1,760 kW / 2,200 kVA 12M55D2000E310 2887 385.9 12192 × 2438 × 3800 23395 Inquire
WBC-2250P 1,800 kW / 2,250 kVA 1,980 kW / 2,475 kVA 12M55D2200E310 3248 434.1 12192 × 2438 × 3800 23410 Inquire
WBC-2500P 2,000 kW / 2,500 kVA 2,200 kW / 2,750 kVA 12M55D2420E310 3609 482.4 12192 × 2438 × 3800 23410 Inquire

Ratings at 50 Hz. Prime: continuous running at a varying load. Standby: emergency use while mains power is out. Ask us for the rating at your site's frequency and altitude.

Specifications

Technical specifications for Prime-Rated Containerized Power Stations
Configuration ISO container (CSC and ISO compliant)
Noise reduction About 25 dB(A)
Rating Prime, with a standby rating
Engine emissions China non-road Stage III
Frequency 50 Hz (60 Hz on request)
Speed (r/min) 1,500
Rated voltage (V) 400 / 230
Power factor 0.8 (lagging)
Phases and connection Three-phase, four-wire, star (Y)
Voltage regulation Automatic (AVR)
Starting method 12 V or 24 V DC electric start

Specifications are indicative only. Final figures follow the manufacturer's data sheet for the configuration quoted.

Product Overview

Each set pairs a diesel engine built for power generation with an alternator and control panel. Choose a size from the model table, or tell us your load and we will recommend one. They suit telecommunications sites, industrial and mining operations, hotels, hospitals and communities.

Product Features

  • Prime power: Rated for continuous running at a varying load, with a standby rating for emergencies.
  • Electronic engine control: Electronically controlled engines with high-pressure common-rail fuel injection meet China non-road Stage III emissions requirements.
  • ISO container: Built to CSC and ISO standards, so it ships and is placed like a standard container.
  • Acoustic design: Acoustic treatment reduces noise by about 25 dB(A).
  • Stable output: Automatic voltage regulation (AVR) keeps the voltage steady as the load changes.

Inquire About This Unit

Tell us your load and location and we will confirm whether this rating is the right fit, then quote it delivered and commissioned.

Request a Quote
same category

Other Containerized Units

Containerized Standby-Rated Containerized Power Stations — 750 – 1,250 kVA
750 – 1,250 kVA · 7 models

Standby-Rated Containerized Power Stations

Standby-rated containerized power stations from 750 to 1,250 kVA.

  • Configuration ISO container (CSC and ISO compliant)
  • Noise reduction About 25 dB(A)
  • Rating Standby (emergency)

Need the right kVA for your load?

Send us your load schedule or a recent electricity bill and we will come back with a sizing recommendation and a delivered-and-commissioned quotation within one business day.